0.28kV~500kV Surge Arresters' Characteristics: 1. The Core column applied winding structure, Polymer Housed core pillar ;
Basic Info.
Model NO. Y10W5-120
Color Brown
Certificate Kema
Delivery Time Shipped in 15 Days After Payment
Transport Package Wooden Case
Trademark YongDe
Origin Zhejiang, China (Mainland)
Production Capacity 1500 Piece/Pieces Per Day
Product Description

0.28kV~500kV Surge Arresters' Characteristics:
1. The Core column applied winding structure, Polymer Housed core pillar molded on the core column, with almost no internal air gap, and outstanding sealing performance Simple in structure, small in size and light in weight.
2. Polymer Housed with silicone rubber, explosion-proof ZnO varistor as the core component is large
in flow capacity.
3. International standard IEC 60099-4 and ANSI 62.22, and with high reliability. With fully insulated tops, the product can be applied to the complete cabinet installation, which can reduce the designing size of cabinet.
4. Products with detachment device can provide signals for quitting operation when failure occurs,
avoiding arrester explosion, and it is maintenance-free.
5. Polymer housed products with a six CTI level, creepage distance meets the requirements of IV level in heavy pollution areas.

Surge Arresters' Technical Parameters:

TypeY10W5-120/313
Rated voltage---------kV1204/10μS High current impulse kA 100
MOCV ----------------kV98Lightning impulse withstand kV550
Nominal Current-------kV10Power frequency voltage withstand(dry/wet)kV230
Residual voltage of steep impulse----at 5kA(kV)3600.1S TOV--------------kV144
8/20μS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV)3041S TOV----------------kV138
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV)23910S TOV---------------kV132
1mA D.C reference voltage (kV)1741200S TOV-------------kV120
Line discharge level3Creepage distance ----mm3906
2mS long duration impulse current A850Material employed in series non-linear resistorZinc Oxide